1. Function
1) A type leakage current protect
2) It can protect the AC leakage, and to the lag voltage
0°、90°、135DC6mA,that is to say what including the harmonic current
will have leakage protection
3) Energy conservation、environmental protection、electronic circuit
module, it can save 2.5mA than the other leakage current switch ,
the electronic circuit solid module which can anti-water, anti-
mildew, anti- quake and etc
4) compare with the traditional AC type leakage current circuit
breaker, it is more full-scale and safer, it can prevent the
accident when the insulation component is damaged and cause the
earth bug
2. Technical parameter
1) Rated current Im (A):32
2) Rated voltage Um (V):230
3) Rated frequency (Hz):50/60Hz
4) Rated connected on-off capacity Im (A):500
5) Rated limited short circuit capacity (A):3000
6) Rated residual operated current I n(mA)
a. Current and voltage when they are same phase: 15I n30
b. Current lag voltage 010.5≤I n≤42
c. Current lag voltage ±907.5I n42
d. Current lag voltage ±1353.3I n42
e.0DC 6mA: 10.5I n42
3. Range of application
1) It is installed in the Factory、Building、
Residential、School、Hospital、Hotel and etc.
2) It is installed in the Inverter Air Conditioner , Ordinary Air
Conditioner , Hot-water electric water heater、Heat pump electric
water heater which the poles are below 5P ,besides , installed in
computer room、vending machine、microwave cooker、fridge 、CT machine
and etc.
3) If they are energy conservation products which have the harmonic
,should install the model.
4. Working condition
1) The ambient air temperature: the upper limited value ≤+40℃, the
lower limited value ≥-5℃,the average temperature ≤+35℃ in 24 hours
2) The atmospheric relative humidity is ≤50% when the ambient air
temperature is +40℃, the humidity is ≤90% at the lower
temperature(≤20
3) Near the installed places, the earth magnetic field can not be
more than 5 times in the any direction
5.Installation
Get off the shield
Faade is upturned,left hand holds the base-side, its thumb and the
third finger press the output side of recession , the thumb and the
third finger of the right hand press the A、B side of the shield,the
forefinger and the third finger hold the shield and pluck upwards ,
then the outer cover will be unslinged
Connect the input line
You must comfirm that the power line of the box is no power , strip
the insulated layer about 9mm, connect the power output line to the
input terminal,connect live wire to L1 according to the
standard,conenct null line to N1,earth line connect to,and must
screw down the three srews , must not connect wrong
Fixture
Install the switch into the cassette of the wall,do not press the
output line,screw down M4 ×25
Connect the output line
According to the Pic 2,connect the output line into the relative
L2、N2、earth terminal,put the output line in the middle of the press
board and the shell,screw down the fixed screw of the two-head .
Dimension